Québec mode. Chapter III values. Amendments are marked QC

Values and rules follow the Quebec Construction Code, Chapter III – Plumbing (NPC 2020 as amended by Québec). Québec amendments are marked QC. Article numbers on pages without that mark are the NPC 2025 ones and may differ slightly in Chapter III.

Size a drainage pipe

Minimum sizes from NPC 2025 Tables 2.4.10.6.-A, -B and -C. Loads are in fixture units (FU).

A drainage pipe that serves a water closet is at least 3 in (2.4.9.2.(1)). In Québec, branches and building drains downstream of the third water closet, and stacks serving more than 6, are at least 4 in (2.4.9.2.(2) and (3)).

Continuous or semi-continuous flow

A pump, air conditioner or other fixture with a continuous flow counts 31.7 FU per L/s (2.4.10.3.(1)). Equipment with a semi-continuous flow takes its load and trap size from Table 2.4.10.12, and so do multiple or manifold condensate drains.